13
Enclosure
13.1
Technical data
Type
Part-No.
Line voltage
Weight
CXE/AV
320053
1 ~ 230 V (-15 % to +10 %), 50/60 Hz
0.9 kg
CXE/AVE
320056
0.65 kg
CXE/AV
320055
2 ~ 400 V (-10 %...+10 %), 50 / 60 Hz
0.9 kg
CXG-24AV
320057
24 V DC +/- 20% (current consumption 65 mA) *
0.75 kg
CXG-24AVE
320058
0.5 kg
*
plus current consumption of connected sensors (at 24 VDC)
Input resistance for sensor or signal
set for the rotational speed (E1, E2)
for 0 - 10 V input: R
i
> 900 k
Ω
for input 4 - 20 mA: R
i
= 250
Ω
(max. load 500
Ω
)
Voltage supply e.g. for sensors
+24 V (-30...+20 %), I
max
70 mA
(for version 24V DC this depends directly on supply voltage)
Analog output (A1, A2 0 - 10 V)
Load resistance (load) > 5 k
Ω
Short-circuit proof, short-circuit current = 24 mA
Digital inputs (D1, D2)
R
i
approx. 7.8 k
Ω
Input current typ. 2.5 mA
Voltage range high level: 7.1...19 V DC
Voltage range low level: 0....2.7 V DC
Max. heat dissipation
approx. 10 W
Max. line fuse
10 A
Max. permissible ambient temperature 55
°
C
Min. permissible ambient temperature 0
°
C (if mains voltage is not switched off up to -20
°
C)
Permissible installation height
0...4000 m amsl
≤
2000 m: no limitation
> 2000 m: max. permissible line voltage = max. voltage indication name plate minus
1.29 % / 100 m
Permissible rel. humidity
85 % no condensation
Electromagnetic compatibility for the
standard voltage 230 / 400 V accord-
ing to DIN IEC 60038
Interference emission EN 61000-6-3 (domestic household applications)
Interference immunity EN 61000-6-2 (industrial applications)
Housing protection
IP54
For type CXE/AV
E
& CXG-24AV
E
(version for panel mounting) only front in built in
condition.
Operating Instructions
UNIcon MODBUS Master
Enclosure
L-BAL-E207-GB 1723 Index 003
Part.-No.
109/114