US Einheiten
The display can be switched between SI units and imperial (US) units =>US units ON.
SI units (factory setting):
°
C, bar, Pa, m
3
/h, K-Factor, m/s
Imperial (US) units:
°
F , psi, in.wg, cfm, K-Faktor US, ft/s
Settings for temperature differences (with SI units in K) are also made for Imperial units
(US) in
°
F (
Δ
1.8
°
F
Δ
1 K).
Conversion factors:
•
Temperature: t /
°
F = 1,8 x t
°
C + 32.
•
Pressure: 1,0 psi = 0,069 bar, 1,0 in.wg = 254 Pa
•
Air
fl
ow: 1,0 cfm = 0.5885 m
3
/h, inlet ring: K-Factor US = 9,3 x K-Factor SI
•
Speed: 1.0 ft/s = 0.3048 m/s
In order to refresh the display, the desired mode must be con
fi
rmed again after switch-
ing over the units (
Base setup)!
OFF
US Einheiten
Start
Reset
Complete re-start of the device
OFF
Reset
Start
Mode
Query of the operating mode (e.g.
1.01
for speed controller)
1.01
Mode
Start
Device name
Display of device name and software version
12.00
xxx
Start
Individual unit number
SN: 154036311039
9.8
Menu group Info
The
fi
rst menu item in the Info menu group is displayed (display dependent on selected mode) after switching on
the line voltage or after exiting the setting menu with the Esc key combination.
Settings cannot be made in this menu group!
Info for mode speed controller
1.01
Info
Level modulation control output.
The percentage modulation factor is displayed in addition to the bar chart.
0 %
Control
Info
Display of the currently active default signal.
The percentage corresponds to the internal actuation of the device under consideration
of the settings
“
Min. speed
”
and
“
Max. speed
”
.
0 - 100 %
0 - 10 V, 10 - 0 V, 0 - 20 mA, 20 - 0 mA, 4 - 20 mA, 20 - 4 mA
0 %
Set external1
Display:
The device operates at:
“
Set external1
”
Signal to
“
E1
”
/
“
GND
”
“
Set external2
”
Signal to
“
E2
”
/
“
GND
”
“
Set Internal1
”
Menu
“
Set Intern1
”
“
Setpoint2
”
Menu
“
Set Intern2
”
Info for mode controller
2.01
...
6.01
Info
Only for mode
2.05
Current actual value difference sensor 1 - sensor 2 (unit depending on the program-
ming).
0
°
C
E1-E2 actual
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
51/114