9.10
IO Setup
9.10.1
Analog outputs
“
A1
”
/
“
A2
”
IO Setup
The analog outputs 0 - 10 V (A1 and A2) can be allocated with various functions.
1. Control signal
(2A)
A1 Function
IO Setup
With the settings
“
A1 min.
”
/
“
A2 min.
”
and
“
A1 max.
”
/
“
A2 max.
”
the characteristic of
the output voltage can be adapted.
Setting range:
“
A1 min.
”
/
“
A2 min.
”
= 0 - 10 V
“
A1 max.
”
/
“
A2 max.
”
= 0 - 10 V
Factory setting:
“
A1 min.
”
/
“
A2 min.
”
= 0 V
“
A1 max.
”
/
“
A2 max.
”
= 10 V
The setting for
“
A1 min.
”
/
“
A2 min.
”
must be below
“
A1 max.
”
/
“
A2 max.
”
.
0.0 V
A1 min.
IO Setup
10.0 V
A1 max.
IO Setup
Inverting of the output voltage is possible with the settings
“
A1 Inverting
”
/
“
A2
Inverting
”
.
Factory setting: Inverting =
“
OFF
”
OFF
A1 Inverting
Function
Description
OFF
no function
Constant voltage 10 V
(1A)
Constant v10 V
Factory setting for
“
A2
”
at operation with one control circuit.
1. Control signal
(2A)
Controlled 0 - 10 V output for control circuit 1 (factory setting for
“
A1
”
)
E1
(3A)
proportional input
“
E1
”
E2
(4A)
proportional input
“
E2
”
Group2
(5A)
Group control (
Controller Setup - group 2)
2.Cooling
(6A)
Only for mode
2.03
temperature controller with additional functions.
Controller output 2 with rising activation at Actual>Nominal =
Cool
.
2.Heating
(7A)
Only for mode
2.03
temperature controller with additional functions.
Controller output 2 with rising activation at Actual<Nominal =
Heat
.
2. control signal
(8A)
Controlled 0 - 10 V output for control circuit 2 (factory setting for
“
A2
”
at operation
with second control circuit).
Control circuit 2 can be activated by programming the E2 function if required (
Base
setup / operation with second control circuit).
Speed
(9A)
proportionally 1.Control signal
Group3
(11A)
Group control (
Controller Setup - group 3)
Group4
(12A)
Group control (
Controller Setup - group 4)
Offset control sig. 1
(14A)
Offset control signal 1
Setting offset
Controller Setup
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.