Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
9.2.3
Functional diagrams temperature control
Example 1: Temperature control in factory setting
“
Cooling function
”
(Idealized principle diagram)
I
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
20 °C
S
10 K
R
30 °C
28.03.2013
v_tempcontrol_cool_cxe_master.vsd
80
70
60
50
40
30
20
10
90
A
n
a
lo
g
O
u
t
[V
]
1
2
3
4
5
6
7
8
9
1
0
M
O
D
B
U
S
O
u
t
[%
]
100
Min.
(Controller Setup:
“
Val > Set = n+
”
to
“
ON
”
)
MODBUS Out:
speed setting over MODBUS
Analog Out:
speed setting over analog output 0 - 10 V
S
Setpoint
R
Pband
I
Actual value
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
34/114