9.10.2.5
Switch over input
“
E1
”
/
“
E2
”
, function
|
4D
|
(operation with one control cicuit)
Switch over between Input signal 1 (Analog In 1 terminal
“
E1
”
) and input signal 2 (Analog In 2 terminal
“
E2
”
).
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
24V
D1 D1
1
0
n = 0- 100 %
0
1
Si 1
Si 2
E1
GND
E2
GND
Si 1
Si 2
26.05.2010
v_4d_umschaltung_e1_e2.vsd
Controller
Si 1
Signal 1
Si 2
Signal 2
For mode speed controller (
1.01
) Base setup for
“
E2 Analog In
”
:
|
1E
|
necessary.
For modes controller (from
2.01
..) Base setup for
“
E2 Analog In
”
:
|
7E
|
necessary (as far as
otherwise does not occupy).
9.10.2.6
Output control circuit 2 additional to
“
A2
”
on
“
A1
”
, function
|
4D
|
The output for control circuit 2 is set additionally to
“
A2
”
to
“
A1
”
(regardless of the programmed function
for
|
A1
|
). Control circuit 1 has no output for the duration of the switching.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
At
“
D1
”
Inverting
“
OFF
”
the output of control circuit 2 also in
fl
uences output
“
A1
”
when the contact is
closed.
1
0
n = 0 - 100 %
03.04.2013
v_4d_contr2_a2_or_plus_a1.vsd
0
1
Controller 1
n = 0 - 100 %
A1
A2
D1
24V
D1
Sensor 1
Controller 2
Sensor 2
9.10.2.7
Set 1/2 or Setpoint 1/2, Function
|
5D
|
For Mode Speed controller
1.01
: Switch over
“
Set Intern1
”
/
“
Set Intern2
”
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
Controller
24V
D1 D1
1
0
n = 40 %
1
n = 80 %
0
- - - - -
- - - - -
11.05.2007
v_5d_vorgabe_intern_1_2.vsd
2
1
1
Setting
“
Set Intern1
”
(depending on device type in: %, Hz, rpm)
2
Setting
“
Set Intern2
”
(depending on device type in: %, Hz, rpm)
•
“
D1 Inverting
”
=
“
OFF
”
:
“
Set Intern1
”
at
opened contact /
“
Set Intern2
”
at closed
contact.
•
“
D1 Inverting
”
=
“
ON
”
:
“
Set Intern1
”
at
closed contact /
“
Set Intern2
”
at opened
contact.
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
68/114