Page 56
TO GET ASSISTANCE, CALL: 919-774-7667
ZENITH PUMPS
74
Zero Speed Logic
Default:
0
Units:
Range:
0~1
75
Primary Positive Offset
Default:
0
76
Primary Negative Offset
Default:
0
77
Secondary Positive Offset
Default:
0
78
Secondary Negative Offset
Default:
0
Units:
Hz
Range:
0~9999
79
Setpoint Mask
Default:
2
Units:
Range:
0
None setpoints disabled;
1
All setpoints disabled
2
Setpoint 2 and 4 disabled;
80
Analog Output Function
Default:
0
Units:
Range:
0~99
It assigns one M (Monitoring) or C (Control) code to the
Analog Output signal. That variable will be routed (via
firmware) to the digital-to-analog converter DAC and
will thus show up on the Analog Output pins.
These are positive and negative offset numbers for
primary and secondary data sets. These allow the
feedback to contain a bias. Only one (positive or
negative) number can be non-zero at any given time.
It dictates the operation of Zero-speed alarm output. If
set to 0, the output is controlled only by the ramped
reference (M-46); if set to 1, the output is controlled by
both the ramped reference (M-46) and the feedback (M-
43).
In other words,
If C74 = 0, ZERO SPEED output is HIGH whenever
Ramped Reference (instantaneous desired speed) is
zero and the output is LOW at all other times.
IF C74 = 1, ZERO SPEED output is LOW whenever
Ramped Reference is non-zero, but does not go HIGH
until both Ramped Reference and Feedback are BOTH
zero.
It determines which setpoints are disabled when keypad
is locked out (J4, pins 1 and 2 shorted).
Содержание ZeDrive
Страница 10: ...Page 9 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Control Cabinet Wiring...
Страница 18: ...Page 17 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Typical Applications Solutions...
Страница 38: ...Page 37 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Trouble shooting Fault Information...
Страница 45: ...Page 44 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Complete Code List...
Страница 59: ...Page 58 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS System Drawings...