![Zenith ZeDrive Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/zenith/zedrive/zedrive_user-manual_3383905048.webp)
Page 47
TO GET ASSISTANCE, CALL: 919-774-7667
ZENITH PUMPS
16
Acceleration Time
Default:
600.0
17
Deceleration Time
Default:
600.0
Units:
Seconds
Range:
0.0~600.0
18
Lag Pulse Limit
Default:
0
Units:
Number of Pulses
Range:
0~9999
19
Lead Pulse Limit
Default:
0
Units:
Number of Pulses
Range:
0~9999
20
Primary Setpoint Maximum
Default:
1800
Units:
eng
Range:
0~9999
21
Secondary Setpoint Maximum
Default:
1800
Units:
eng
Range:
0~9999
These parameters control the rate at which the desired
speed is ramped up/down. It is the number of seconds
required to change the motor speed by 1800 RPM.
Default value of 600 seconds assures proper lubrication
of a new pump. After the initial startup period, operating
values can be much lower.
Acc. Time below 0.5 second are not recommended
It sets a maximum pulse error count for the difference
between idealized feedback pulses minus the Feedback
pulses. It may not always be desirable to recover all the
position error lag. Set this paramter to the desired lag
pulse limit.
It sets a maximum pulse error count when the Feedback
pulses exceed the idealized feedback pulse count. Set
this parameter to the desired lead pulse limit.
This parameter establishes full-scale speed when one of
the primary setpoints is active. It is in the same units as
C01 and C02. The format of the number entered here
(number of digits to the right of decimal point)
establishes the setpoint format. When the controlled
process is at this speed, the Motor Shaft Speed will be at
C34 (Max RPM Feedback - Primary)
This parameter establishes full-scale speed when one of
the secondary setpoints is active. It is in the same units
as C03 and C04. The format of the number entered here
(number of digits to the right of decimal point)
establishes the setpoint format. When the controlled
process is at this speed, the Motor Shaft Speed will be at
C37 (Max RPM Feedback - Secondary)
Содержание ZeDrive
Страница 10: ...Page 9 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Control Cabinet Wiring...
Страница 18: ...Page 17 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Typical Applications Solutions...
Страница 38: ...Page 37 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Trouble shooting Fault Information...
Страница 45: ...Page 44 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS Complete Code List...
Страница 59: ...Page 58 TO GET ASSISTANCE CALL 919 774 7667 ZENITH PUMPS System Drawings...