YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 35
NJEX 7300G ver.08-2018
Section 6: Programming for Proportional-to-Time Operation
Or
Or
it has been loaded into memory, the High Level value
will begin to flash. Use the
Up Arrow
key to increase
the value and the
Down Arrow
key to decrease the de-
sired value. This alarm should typically be set at less
than 80%. When a new value has been chosen, press
the
Enter
key to store the new High Level Alarm setting
into memory. Press the
Down Arrow
key to advance
to the next menu.
Expansion Tank Pressure Monitoring
The expansion tank pressure should typically remain at
approximately 25 psi
(1.72 Bar)
. There are two alarms
that can be triggered a High Pressure Expansion Tank
Alarm, and a Low Pressure Expansion Tank Alarm.
1.
Disabled:
no expansion tank pressure monitoring,
0 = disabled, Both Low & High settings must be
disabled
. Normal operation should have this func-
tion enabled.
2.
Enabled:
Low Level should typically be set @ 23
psi
(1.58 Bar)
, but is adjustable from 0 psi
(0 Bar)
up to the high level set point. High Level should
typically be set @ 27 psi
(1.86 Bar)
, but is adjust-
able from 0 psi
(0 Bar)
up to 99 psi
(6.82 Bar)
.
To set the alarm level points
,
figure 66
, press and re-
lease the
Select
key. The Low Pressure value will be-
gin to flash when chosen. Use the
Up Arrow
key to in-
crease the value and the
Down Arrow
key to decrease
the value. When a new value has been chosen, press
the
Enter
key to store the new Low Pressure setting
into memory. The entered value will stop flashing when
it has been loaded into memory and the High Pressure
value will begin to flash. Use the
Up Arrow
key to in-
crease the value and the
Down Arrow
key to decrease
the value. When a new value has been chosen, press
the
Enter
key to store the new High Pressure setting
into memory. Press the
Down Arrow
key to advance
to the next menu.
Odorant Inlet Pressure Monitoring
In order for the fill valve to function correctly a pressure
differential between the Bulk Odorant Storage Tank
and the Expansion Tank, must be maintained. This
differential should never be less than 5 psi
(.35 Bar)
and typically not more than 10 psi
(.69 Bar)
. There are
two alarms that can be triggered from the Odorant Inlet
Pressure reading, a High Odorant Inlet Alarm, and a
Low Odorant Inlet Alarm,
figure 67
.
pmp bat vmtr sig tnk
Expansion Tank (psi)
20.0=Low 30.0=High
pmp bat vmtr sig tnk
Expansion Tank (bar)
1.40=Low 2.00=High
Figure 66
Figure 67
pmp bat vmtr sig tnk
Expansion Tank (bar)
1.40=Low 2.00=High
pmp bat vmtr sig tnk
Expansion Tank (psi)
20.0=Low 30.0=High
Содержание NJEX 7300G
Страница 1: ...NJEX 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M ...
Страница 2: ......
Страница 3: ...The NJEX 7300G Instruction Operating Manual Version 08 2018 ...
Страница 4: ......
Страница 10: ......
Страница 129: ...201 Ivyland Road Ivyland PA 18974 800 344 5399 P 281 362 6500 F 281 362 6513 Sales yzhq com www yzsystems com ...