Section 8: Working with the N-300 System Displays
Figure 126
Figure 128
pmp bat vmtr sig tnk
Meter Level 100.0%
*Fill
pmp bat vmtr sig tnk
Meter Level 00.0%
*Fill
pmp bat vmtr sig tnk
Fill Verometer?
*No *Yes
pmp bat VMTR sig tnk
Meter Level 0.0%
*Fill
Umtr-Cable
pmp bat VMTR sig tnk
Meter Level 0.0%
*Fill
No Fill
pmp bat VMTR sig tnk
Meter Level 0.0%
*Fill
Slow Fill
pmp bat VMTR sig tnk
Meter Level 106.1%
*Fill
Flvalve-Fail
pmp bat VMTR sig tnk
Meter Level 99.6%
*Fill
OdorInlet-Cabl
pmp bat VMTR sig tnk
Meter Level 99.6%
*Fill
Odor Inlet-Low
pmp bat VMTR sig tnk
Meter Level 99.6%
*Fill
Odor Inlet-Hi
pmp bat VMTR sig tnk
Meter Level 99.6%
*Fill
XTank-Cable
pmp bat VMTR sig tnk
Meter Level 99.6%
*Fill
XTank-Low
pmp bat VMTR sig tnk
Meter Level 99.6%
*Fill
XTank-High
pmp bat VMTR sig tnk
Meter Level 104.3%
*Fill
Over-fill
pmp bat VMTR sig tnk
Meter Level 104.3%
*Fill
Fillrate
Figure 127
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Figure 128
Meter Level –
Verometer
This display illustrates the Verometer level in percent.
As odorant is pumped out of the Verometer, the N-300G
controller will automatically refill the meter when the
meter level reaches 0%,
figure 126
.
To manually fill the Verometer,
figure 127,
press the
*Fill
key and follow the instructions. The following rep-
resent There conditions that will result in a meter alarm
indication.
Meter Alarms –
Verometer
These are of the displays containing 12 alarm and non-
alarm indicators,
figures 128
, to provide information on
Verometer operation.
•
Vmtr-Cable,
the Verometer cable is not communicat-
ing to the controller.
•
No Fill,
the meter has failed to fill.
a. The meter has failed to fill to 100% within six
minutes
b. The fill was inhibited due to leakage detection
•
Slow Fill,
the meter has failed to fill within three min-
utes.
•
Fill Valve
, the fill valve has failed to close.
•
OdorInlet-Cable,
inlet fill valve pressure transmitter is
not communicating with the controller.
•
OdorInlet Lo,
the required inlet pressure of odorant is
lower than allowed.
•
OdorInlet Hi,
the required inlet pressure of odorant is
higher than allowed
•
XTank-Cable,
the expansion tank cable outlet fill valve
pressure transmitter is not communicating with the con-
troller.
•
XTank Low,
the expansion tank pressure has fallen
below the programmed low-pressure setting.
•
XTank Hi,
the expansion tank pressure has risen
above the programmed high-pressure setting.
Meter Indicators, non-alarm
•
Over Fill,
the meter has been filled in excess of 112%.
a. The Verometer Fill Rate is too fast, in excess of
10 seconds.
b. The verometer Fill Valve has failed to close.
•
Fill Rate,
the meter has filled too fast, in excess of
10 seconds.
Содержание NJEX 7300G