Section 5: Programming for Proportional-to-Flow Operation
Or
pmp bat vmtr sig tnk
Expansion Tank (psi)
20.0=Low 30.0=High
pmp bat vmtr sig tnk
Expansion Tanks (bar)
1.40=Low 2.00=High
Figure 51
Or
pmp bat vmtr sig tnk
Odorant Inlet (psi)
25.0=Low 40.0=High
pmp bat vmtr sig tnk
Odorant Inlet (bar)
1.70=Low 2.80=High
Figure 52
To set the alarm level points
,
figure 51,
press and
release the
Select
key. The Low Pressure value
will begin to flash when chosen. Use the
Up Arrow
key to increase the value and the
Down Arrow
key
to decrease the value. When a new value has been
chosen, press the
Enter
key to store the new Low
Pressure setting into memory. The entered value will
stop flashing when it has been loaded into memory.
Next the High Pressure value will begin to flash. Use
the
Up Arrow
key to increase the value and the
Down
Arrow
key to decrease the value. When a new value
has been chosen, press the
Enter
key to store the
new High Pressure setting into memory. Press the
Down Arrow
key to advance to the next menu.
Odorant Inlet Pressure Monitoring
For the fill valve to function correctly a pressure dif-
ferential between the Bulk Odorant Storage Tank and
the Expansion Tank, must be maintained. This dif-
ferential should never be less than 5 psi
(.35 Bar)
and
typically not more than 10 psi
(.69 Bar)
. There are two
alarms that may be triggered from the Odorant Inlet
Pressure reading, a High Odorant Inlet Alarm, and a
Low Odorant Inlet Alarm.
To set the alarm level points
,
figure 52,
press and
release the
Select
key. The Odor Inlet Low value will
begin to flash when chosen. Nominal low pressure in
the Odorant Storage Tank is 30 psi
(2.07 Bar)
. Use
the
Up Arrow
key to increase the value and the
Down
Arrow
key to decrease the value. When a new value
has been chosen, press the
Enter
key to store the
new Odor Inlet Low setting into memory. The entered
value will stop flashing when it has been loaded into
memory. Next the Odor Inlet High value will begin to
flash. Nominal high pressure in the Odorant Stor-
age Tank is 35 psi
(2.41 Bar)
. Use the
Up Arrow
key
to increase the value and the
Down Arrow
key to
decrease the value. When a new value has been
chosen, press the
Enter
key to store the new Odor In-
let High setting into memory. Press the
Down Arrow
key to advance to the next menu.
Содержание NJEX 7300G
Страница 1: ...NJEX 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M ...
Страница 2: ......
Страница 3: ...The NJEX 7300G Instruction Operating Manual Version 08 2018 ...
Страница 4: ......
Страница 10: ......
Страница 129: ...201 Ivyland Road Ivyland PA 18974 800 344 5399 P 281 362 6500 F 281 362 6513 Sales yzhq com www yzsystems com ...