Appendix B: N-300 Modbus Specifications
Communications Settings
Protocol ............................................................................. Modbus
Data framing ...................................................................... Modbus RTU and ASCII
Slave Address range ......................................................... 0-247, 0 = Modbus disabled
Baud rates ......................................................................... 1200, 2400, 4800, and 9600
Number of data bits ........................................................... 7 or 8
Parity ................................................................................. None, Odd, Even
Stop bits:
...........................................................................
1 or 2
Serial communications: ..................................................... Redundant RS-485 2 wire
N300 Modbus Function Support
Function Code
Function
Description
1
..............................
Read Coil Status ..................Reads the ON/OFF status of discrete outputs (coils)
3..............................
Read Holding Registers .......Reads the binary contents of holding registers
5..............................
Force Single Coil .................Forces a single coil to either the ON or OFF state
6..............................
Preset Single Registers .......Presets a value into a single holding register
16
............................
Preset Multiple Registers Presets values into a sequence of holding registers
Boolean Registers
The Boolean data type could be used for status, and control. The discrete outputs or “coils” as defined by the
Modbus specification are read/write registers. This ON/OFF data type can be manipulated using Modbus func-
tions 1 and 5.
The valid address range for this data type is 00001 to 09999.
Function 1,
allows reading a single coil per query
Function 5,
allows writing single or multiple coils per query.
Control Functions
The control functions available via Modbus are listed below. The registers are accessed using Modbus func-
tions 1 and 5. The master device can initiate a state change by setting a control coil. The N300 controller
will clear non-toggle type coils to acknowledge the state change has been acted upon. Toggle type coils hold
their current state until changed either locally or remotely. The local/remote load cycle control (00007) deter-
mines whether a load cycle can be initiated via contact closure (local) connected to the load cycle inputs on the
controller or
by Modbus coil 00006 (remote). These coils are only active in an N300 Liquid system. Coil 00011
determines whether a remote inhibit can be initiated by a contact closure (local) connected to the inhibit inputs
on the controller or by Modbus coil 00010 (remote).
Coil 00009 is used to save all the current parameters to
the controller EEPROM.
IMPORTANT:
Coil 00009, must be used to save any parameters that were changed via Modbus.
Address Access
Description
00001
............
Read/Write .............. Start/Stop the pump (toggle)
00002
............
Read/Write .............. System Standby (toggle)
00003
............
Read/Write .............. Reset Accumulated Stroke Count
00004
............
Read/Write .............. Reset Accumulated Odorant Injected
00005
............
Read/Write .............. Fill Verometer (toggle)
00006
............
Read/Write .............. Start/Stop a Load Cycle (toggle) (Liquid System Only)
Appendix B: N-300 Modbus Specifications
Содержание NJEX 7300G
Страница 1: ...NJEX 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M ...
Страница 2: ......
Страница 3: ...The NJEX 7300G Instruction Operating Manual Version 08 2018 ...
Страница 4: ......
Страница 10: ......
Страница 129: ...201 Ivyland Road Ivyland PA 18974 800 344 5399 P 281 362 6500 F 281 362 6513 Sales yzhq com www yzsystems com ...