YZ Systems Milton Roy • 201 Ivyland Road • Ivyland, Pennsylvania • USA • 18974 • P: 281.362.6500 • www.yzsystems.com
Page 36
NJEX 7300G ver. 08-2018
Section 6: Programming for Proportional-to-Time Operation
Setting Operator Input Parameters,
Continued
To set the alarm level points,
figure 68
, press and
release the
Select
key. The Odorant Inlet Low value
will begin to flash when chosen. Nominal low pressure
in the Odorant Storage Tank is 30 psi
(2.07 Bar)
. Use
the
Up Arrow
key to increase the value and the
Down
Arrow
key to decrease the value. When a new value
has been chosen, press the
Enter
key to store the
new Odorant Inlet Low setting into memory. The en-
tered value will stop flashing when it has been loaded
into memory and the Odorant Inlet High value will
begin to flash. Nominal high pressure in the Odorant
Storage Tank is 35 psi
(2.41 Bar)
. Use the
Up Arrow
key to increase the value and the
Down Arrow
key
to decrease the value. When a new value has been
chosen, press the
Enter
key to store the new Odorant
Inlet High setting into memory. Press the
Down Ar-
row
key to advance to the next menu.
Alarm to Relay Delay
Is a programmable time that can be entered to allow
for a period of time to occur between the initial issu-
ance of an alarm and the actual remote reporting of
the alarm via the alarm relay output.
1. 0 = No Relay Contact Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Relay Contact will oc-
cur
To set the alarm delay time
,
figure 69
, press and
release the
Select
key. The Alarm to Delay value
will begin to flash when chosen. Use the
Up Arrow
key to increase the value and the
Down Arrow
key
to decrease the value. When a new value has been
chosen, press the
Enter
key to store the value.
Alarm to Call Out Delay
Is a programmable time that can be entered to allow
for a period of time to occur between the initial issu-
ance of an alarm and the actual automatic call out
function via a modem or Modbus communication port.
1. 0 = No Alarm Call Out Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Call Out will occur
Or
Figure 68
Figure 69
pmp bat vmtr sig tnk
Odorant Inlet (psi)
25.0=Low 40.0=High
pmp bat vmtr sig tnk
Odorant Inlet (bar)
1.70=Low 2.80=High
pmp bat vmtr sig tnk
Alarm to Relay Delay
0 minutes
pmp bat vmtr sig tnk
Alarm to Callout Dly
0 minutes
Содержание NJEX 7300G
Страница 1: ...NJEX 7300G N A T U R A L G A S O D O R I Z A T I O N S Y S T E M ...
Страница 2: ......
Страница 3: ...The NJEX 7300G Instruction Operating Manual Version 08 2018 ...
Страница 4: ......
Страница 10: ......
Страница 129: ...201 Ivyland Road Ivyland PA 18974 800 344 5399 P 281 362 6500 F 281 362 6513 Sales yzhq com www yzsystems com ...