Table 6.7p Parameter Functions
No.
Name
Function/Use
Default
Setting Range
P458 Pressure Sensor Span
1250
0 to 9999 × 0.1 %
P459 Pressure Sensor Zero
Adjusts the zero point/span of pressure sensor input voltage.
According to the output voltage specification of the pressure
sensor, set the parameters as follows.
Pressure Sensor
Zero
Pressure Sensor
Span
Pressure Sensor
Output Voltage
P459
P458
0.5 to 4.5 V
500
1250
0 to 5 V
0
1000
1 to 5 V
1000
1250
* By default, the values for 0.5 to 4.5 V are set.
500
- 999 to 9999
Mv
P460 Rated
Pressure
Sets the pressure at a pressure command voltage of DC + 5 V.
This parameter is used to change the rated pressure without
changing the pressure command voltage.
When pressure monitoring (SMP) is selected for AM monitoring
output, the set pressure is output at DC + 5 V.
175
1 to 300
× 0.1 MPa
P461 Rated Motor Speed
Sets the motor speed at a flow command voltage of DC + 5 V.
This parameter is used to change the rated motor speed
without changing the flow command voltage.
When motor speed monitoring (SMN) is selected for AM
monitoring output, the set motor speed is output at DC + 5 V.
2000
1 to 3000
r/min
0.0
17.5
Pressure
[MPa]
5.0 [V]
PIN Command
0.0
2000
Motor Speed
[r/min]
5.0 [V]
QIN Command