EM-0146-8
- -
42
Table 6.7b Parameter Functions
No.
Name
Function/Use
Default
Setting Range
P 52
Operation Panel
Display Data Selection
Selects a monitoring item to be displayed on the operation
panel and a monitoring item to be output to the terminal FM.
* See “Table 6.7b-1” below.
0/
(100)
0, 5 to 14, 17, 20, 23,
25, 55, 81 to 86, 100
Table 6.7b-1 Operation Panel Display Data Selection
Monitoring Item
Setting Value
Unit
Description
Output Voltage
0/100
V
Output voltage supplied to the motor side.
Rotation Command
5
1 r/min
Speed command.
Motor Speed
6
1 r/min
Motor speed.
Motor Torque
7
0.1 %
Torque value with the rated motor torque taken as 100 %.
Converter Output Voltage
8
0.1 V
DC bus voltage value.
Dynamic Brake Utilization
9
0.1 %
Rate of dynamic brake utilization set by the setting parameters “P_30”
and “P_70.”
Electronic Thermal Load
Factor
10 0.1
%
Accumulative value of motor thermal load with the electronic thermal
triggering level taken as 100 %.
Output Current Peak
11
0.1 A
Retains the peak value for output current monitoring (memory is reset
every time the unit starts up).
Converter Output Voltage
Peak
12 0.1
V
Retains the peak value of DC bus voltage (memory is reset every time
the unit starts up).
Input Voltage
13
0.01 kW
Voltage on the AMSE controller input side.
Output Voltage
14
0.01 kW
Voltage on the AMSE controller output side.
Load Meter
17
0.1 %
Displays the torque current with the set value of “P_56” taken as
100 %.
Accumulative Power-on
Time
20 1
h
Accumulates the power-on time (0.001 = 1h: the value returns to 0 h
after reaching 65,535 h (max.)).
Actual Operating Time
23
1 h
Accumulates the operating time (0.001 = 1 h: the value returns to 0 h
after reaching 65,535 h (max.).
Accumulative Power
Consumption
25 0.01
kW
Displays the accumulative power consumption based on the
monitored output voltage.
Input Terminal Status
-
Displays the “
ON
/
OFF
” status of the control circuit input terminals on
the operation panel. See “Fig. 6.7a” below for display details.
Output Terminal Status
55
-
Displays the “
ON
/
OFF
” status of the control circuit output terminals on
the operation panel. See “Fig. 6.7a” below for display details.
Pressure Input Command
81
0.01 V
Pressure command voltage.
Flow Input Command
82
0.01 V
Flow command voltage
AM Terminal Output
83
0.01 V
Outputs an item selected by the setting parameter “P463.”
Manufacturer-controlled
-
-
An output value is invalid.
Manufacturer-controlled
-
-
An output value is invalid.
Manufacturer-controlled
-
-
An output value is invalid.
RL
RM
RH
RT
AU
STOP MRS
RES
STF STR
JOG
CS
ABC1
ABC2
RUN SU
IPF
OL FU
Reserved
Reserved
Reserved
Reserved
Reserved
Input Terminal
Output Terminal
Fig. 6.7a Status of Input/Output Terminals