The rate of each GOES Self-Timed Output directly affects how much data will be sent with each
transmission. For example, if transmissions are scheduled for every hour, having an Output Rate
of 15 minutes (00:15:00) will allow the past four values (60/15 = 4) to be sent each transmission.
Changing the Output Rate to every 5 minutes (00:05:00) would allow the past 12 values (60/5 =
12). In the above screen, through the Task is scanning every minute (indicated by the Input
Rate), a much slower Timed Rate (such as 15 minutes) would be preferable to fit within the
allowed GOES transmit buffer. Timed Rates should always be a multiple of the Input Scan Rate.
The GOES Random Output is not based on a timed rate and thus has no timing options. The
Output simply runs after each scan measuring the Task, using the Transmit Condition statement
set within the Random Options to determine if a Random transmission should be sent.
The remainder of the GOES Output Properties screens share similar buttons and labels.
Transmitting this Task:
By default, the Task will not be added to the GOES transmission until
explicitly told to do so through the GOES Properties screens. The simplest way to do this is by
pressing the Add to Transmission button. Once the Task has been added and saved as part of the
GOES transmission, the label will change to Yes.
GOES Radio Mode:
The current GOES mode is displayed here. If a mode is selected that does
not allow the current Task value to be transmitted, the mode will appear in red. For example, if
the GOES Mode is set to Random, no Self-Timed transmissions will be sent. Thus on the GOES
Self-Timed Properties screen, the Mode will appear as Random, highlighted in red. The Mode
can be changed through the GOES Configuration screen.
General GOES:
Provides quick access to the GOES Configuration and specific Self-Timed or
Random Options. These are the same screens that appear in the GOES Configuration.
Self-Timed/Random Data:
Provides quick access to the Data Settings and/or actual Data Setup
for the GOES Self-Timed and Random transmissions. These are the same screens that appear in
the GOES Configuration.
System 5000
Outputs 6-9
TM
Содержание WaterLog Series
Страница 1: ...Model System 5000TM Owner s Manual Revision 1 4 2...
Страница 2: ......
Страница 8: ......
Страница 24: ...2 10 Hardware Overview System 5000TM...
Страница 58: ...5 14 Inputs System 5000TM...
Страница 128: ...10 14 System Setup General Setup System 5000TM...
Страница 144: ...12 6 System Setup Inputs Outputs System 5000TM...
Страница 168: ...14 4 Maintenance and Troubleshooting System 5000TM...
Страница 170: ...A 2 System 5000 Specifications System 5000TM...
Страница 172: ...B 2 Pressure Sensor Option Module Specifications System 5000TM...
Страница 174: ...C 2 Analog Digital Option Module Specifications System 5000TM...