YORK INTERNATIONAL
36
(YCHA100)
PROBLEM
CAUSE
SOLUTION
F4 Fault
1. Condenser fans not operating
1. Check fans, Fuses, and Contactors.
Code Cuts out on High Dis-
or rotating backwards.
Air flow must be “up”.
charge Pressure as sensed 2. Too much refrigerant
2. Remove Refrigerant
by Microprocessor via
3. Air in refrigerant system
3. Evacuate and recharge
high discharge pressure
4. Defective Discharge Press. Transducer
4. Replace Discharge Press. Transducer
transducer.
5. Defective Relay Output Board
5. Replace Relay Output Board (Contact
NOTE: If external H.P.
the local YORK service representative.)
Cut-out Switch trips
6. Defective Analog Input Board
6. Replace Analog Input Board (Contact
the Fault Code will be
the local YORK service representative.)
an F1.
F9 Fault Code
1. Temperature sensed incorrectly
1. Verify actual ambient temperature
Cuts out on high ambient
by thermistor
at probe.
temperature. (Max.=
2. Fans Rotating Backwards
2. Air flow must be “up”. Correct fan
130°F. Will re-start auto-
rotation.
matically if temperature
3. Air flow to unit restricted (or
3. Check installation clearances.
drops below 130°F)
being re-circulated)
(See page 4)
F10 Fault Code
1. Temperature sensed incorrectly
1. Verify actual ambient temperature
Cuts out on Low Ambient
by thermistor.
at probe.
Temperature (35°F min.
2. Check Low Ambient Temp. Cut-out
2. Adjust if necessary.
for Std. Unit. 0°F min.
setting on display (Display Code 7)
for Low Ambient Unit.)
NOTE: Operation below
35°F requires Low Am-
bient Accessory Kit
Follow steps listed under GENERAL above to verify cutout set point and actual cutout reading. Factory Setting = 36°F
(or as appropriate for brine).
F11 Fault Code
1. Check LWT Cutout Point on Panel.
1. Adjust if necessary, and restart unit.
Low Water
2. Defective LWT or RWT sensor
2. Check according to following table
Temperature Shutdown
(use digital volt meter)* Replace if
necessary.
Temp.° F
Voltage-(DC)
30.9
1.67
33.6
1.79
36.3
1.91
38.9
2.03
41.4
2.15
43.9
2.28
46.3
2.40
48.6
2.52
50.8
2.64
53.0
2.76
55.1
2.89
57.2
3.01
59.3
3.13
61.3
3.25
63.2
3.37
*Check voltage on Analog Input Board
LWT: J20-1 to J20-3
RWT: J21-1 to J21-3
Содержание YCAQ10
Страница 20: ...YORK INTERNATIONAL 20 LD01779 YCHA100 FIG 9 WIRING DIAGRAM YCHA100...
Страница 21: ...FORM 150 40 NM20 21 YORK INTERNATIONAL YCHA100 LD01779 D...
Страница 22: ...YORK INTERNATIONAL 22 LD01780 L YCHA100 FIG 9 Continued...
Страница 23: ...FORM 150 40 NM20 23 YORK INTERNATIONAL LD01780 R YCHA100...
Страница 24: ...YORK INTERNATIONAL 24 YCHA100 LD01781 FIG 9 Continued...
Страница 25: ...FORM 150 40 NM20 25 YORK INTERNATIONAL LD01782 YCHA100...
Страница 46: ...YORK INTERNATIONAL 46 LD01787...
Страница 47: ...FORM 150 40 NM20 47 YORK INTERNATIONAL LD01788...
Страница 48: ...YORK INTERNATIONAL 48 LD01789...
Страница 49: ...FORM 150 40 NM20 49 YORK INTERNATIONAL LD01790...
Страница 50: ...YORK INTERNATIONAL 50 LD01791...
Страница 51: ...FORM 150 40 NM20 51 YORK INTERNATIONAL LD01792...
Страница 77: ......
Страница 78: ......
Страница 79: ......
Страница 80: ......
Страница 81: ......
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......