YORK INTERNATIONAL
5
FORM 155.16-O3
it and opens when the level decreases below the float,
and 1F is at a higher level than 3F, it is not possible that
1F would be closed if 3F is still open; unless one of the
switches is stuck in one position. If this condition is de-
tected, a safety shutdown is performed and “DAY-TIME-
REF PUMP FLOAT SW CONFLICT” is displayed. NOTE:
the state of each float switch is not recognized as being
valid until it has been in the same position for the dura-
tion of the respective float switch timer. 1F is determined
by REFRIGERANT PUMP STARTUP DELAY setpoint
timer; 3F is determined by REFRIGERANT PUMP
SHUTDOWN DELAY setpoint timer. Therefore, the float
switch conflict will be allowed to exist for the duration of
the respective timer, depending upon which float switch
is causing the conflict.
The refrigerant level solenoid (unloader control) valve is
energized (open) whenever the refrigerant level float
switch opens and the leaving water temperature is less
than 5°F (2.8°C) above setpoint. If the refrigerant tem-
perature is above 34.0°F (1.1°C), the solution (absorber
on 50 Hz Models YIA-10E3 – YIA-14F3 with Franklin
pumps) pump is also turned on. If however, the refriger-
ant temperature falls below 34.0°F (1.1°C), the solution
(absorber on 50 Hz Models YIA-10E3 – YIA-14F3 with
Franklin pumps) pump is turned off and will not turn on
until the refrigerant temperature has risen above 35.5°F
(1.9°C). If the refrigerant temperature is above 36.0°F
(2.2°C), the stabilizer refrigerant solenoid valve is de-
energized (closed). Coincidental with the opening of the
steam or hot water stop valve, if selected by the opera-
tor, a software timer is initiated, limiting the steam or hot
water control valve actuator opening, delaying the auto-
matic temperature-controlled operation of the actuator.
This function prevents excessive steam or hot water use
during unit pulldown, allowing the unit to ramp up to match
the load over an adjustable 0 to 255 minute interval. This
feature is called the Pulldown Demand Limiter. At the
conclusion of the pulldown interval or whatever the
pulldown limit is not exceeded, unit loading is controlled
by the automatic temperature control algorithm.
The minimum position of the modulating steam or hot
water valve is programmable from 10-20% valve posi-
tion. The micro panel varies the load by pulsing the steam
or hot water control valve actuator close and open to
control chiller capacity from the programmed lower limit
(10 - 20%) to 100%. At unit shutdown, the steam or hot
water control valve is driven closed. A potentiometer on
the valve provides position feedback to the micro panel,
which is displayed on the keypad via the DISPLAY DATA
key. System start is only allowed when the steam or hot
water control valve is unloaded below 10%. Steam or
hot water units are used for cooling only. All units can be
manually controlled (LOAD, UNLOAD, HOLD) in SER-
VICE mode from the keypad. When a unit is commis-
sioned, it is sometimes necessary to limit the maximum
load. This is accomplished by entering the special ac-
cess code to enter PROGRAM mode. Via the LOAD key,
the Service Engineer can program the MAXIMUM
COOLING LOAD and from 50 to 100%. The default value
is 100%. When the unit is operating, if the maximum load
is reached, the message displayed is “SYSTEM RUN -
MAXIMUM COOLING”.
During operation, the refrigerant temperature sensor,
which is continuously monitored and displayed, provides
several control functions. If the refrigerant temperature
falls to 35.5°F (1.9°C), the stabilizer refrigerant solenoid
valve (2SOL) is energized (open) on units equipped with
Franklin pumps; if the unit is equipped with Buffalo pumps,
it will be energized only if the refrigerant pump is run-
ning. This transfers refrigerant to the generator’s solu-
tion outlet line to reduce the concentration, thus reduc-
ing the cooling capacity of the unit. This lessens the pos-
sibility of crystallization. Simultaneously, the warning
message “LOW REFRIGERANT TEMPERATURE” is
displayed via the STATUS key and unit loading is inhib-
ited. If the temperature falls to 34.0°F (1.1°C), the solu-
tion (absorber on 50 Hz Models YIA-10E3 – YIA-14F3
with Franklin pumps) pump turns off; this should allow
the refrigerant temperature to rise. If the refrigerant tem-
perature rises to 35.5°F (1.9°C), the solution pump turns
on. If the refrigerant temperature rises to 36.0°F (2.2°C),
the stabilizer refrigerant solenoid valve is de-energized
(closed), and the unit loading inhibit is removed. How-
ever if the refrigerant temperature continues to fall, a
low refrigerant temperature safety shutdown occurs at
33.0°F (.5°C). If the unit experiences a shutdown when
the refrigerant temperature is 34°F (1.1°C) or below, the
chilled water pump continues to run for a minimum of 30
minutes. Subsequently, when the refrigerant tempera-
ture rises to 37.0°F (2.8°C), the dilution cycle begins.
The motor coolant solenoid valve (units with Franklin
pumps only) is energized (open) whenever the strong
solution temperature is above 160°F (71.1°C) (on units
equipped with EPROM version A.02F.02 or later, this
threshold is programmable from 127°F to 160°F (52.8 to
71.1°C); the threshold should only be programmed by a
qualified service technician following instructions in “Ser-
vice” manual, Form 155.16-M3). The solenoid is de-en-
ergized (closed) whenever the strong solution tempera-
ture is below 150°F (65.6°C) (on units equipped with
EPROM version A.02F.02 or later, the close threshold is
equal to the programmed open threshold minus 10°F).
The purpose of the valve is to prevent evaporation of
water from the float chamber during unit shutdown or
when the unit operates at low load and low condensing
water temperatures. However, if the refrigerant and so-
lution (absorber and generator on 50 Hz Models YIA-
10E3 – YIA-14F3 with Franklin pumps)
pump motor cool-
ant level float switch opens, the unit locks out on a safety
shutdown.
A feature limits the steam or hot water control valve open-
Содержание MILLENNIUM YIA-HW-14F3
Страница 116: ...YORK INTERNATIONAL 115 FORM 155 16 O3 NOTES...
Страница 117: ...116 YORK INTERNATIONAL NOTES...