24
YORK INTERNATIONAL
EPROM
VERSION
A.02F.02
OR
LATER
CLOSE ALARM CONTACTS
TB4-89/90 TO SOUND AUDIBLE
ALARM UNTIL RESET WITH
“WARNING RESET” KEY
< 6 PSIA
(41.4 kPa)
PUT HIGH GENERATOR PRESSURE
OVERRIDE IN EFFECT-LIMIT
STEAM/HOT WATER VALVE
POSITION TO 30%
HIGH GEN
PRESSURE
OVERRIDE IN
EFFECT
REMOVE “HIGH GENERATOR PRESSURE
OVERRIDE” -ALLOW UNIT LOADING TO
>30% STEAM/HOT WATER VALVE POSITION
CLEAR “HIGH GENERATOR PRESSURE
OVERRIDE” WARNING MESSAGE WHEN
WARNING RESET PRESSED IN SERVICE MODE
CHECK AUTO-DECRYSTALLIZATION
(ADC) TEMP @ RT2
>160°F
(71.1°C)
START 10-MINUTE
ADC TIMER
NORMAL
ADC IN
EFFECT
SECOND-
ARY LIMITED
ADC IN
EFFECT
PRIMARY
LIMITED
ADC IN
EFFECT
➤
➤
➤➤
➤
➤
➤➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
YES
YES
YES
YES
YES
YES
➤
YES
NO
NO
NO
NO
NO
A
B
A
B
C
D
E
F