![York MILLENNIUM YIA-HW-14F3 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/york/millennium-yia-hw-14f3/millennium-yia-hw-14f3_operation-manual_912660019.webp)
18
YORK INTERNATIONAL
LCWT <
PREVIOUS
SP-2
LCWT
< SP-2
< 30
MINUTES
SINCE LCWT
SP RAISED
LOW WATER TEMP
SHUTDOWN
THRESHOLD = PREVIOUS
SETPOINT-2
CHECK MULTI-UNIT
CYCLING INPUT @ TB2-9
CLOSED
CHECK REMOTE/LOCAL
CYCLING INPUT @ TB2-13
CLOSED
CHECK AUXILIARY
SAFETY SHUTDOWN
INPUT @ TB-31
15
PAGE 49
SAFETY SHUTDOWN-DISPLAY
“DAY-TIME-AUXILIARY SAFETY
SHUTDOWN” AS STATUS
16
PAGE 50
CYCLING SHUTDOWN- DISPLAY
“DAY-TIME-SYSTEM CYCLING
AUTOSTART” AS STATUS
14
PAGE 48
CYCLING SHUTDOWN-DISPLAY
“DAY-TIME-LOW WATER
TEMP-AUTOSTART”
AS STATUS
➤
➤➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
A
A
Содержание MILLENNIUM YIA-HW-14F3
Страница 116: ...YORK INTERNATIONAL 115 FORM 155 16 O3 NOTES...
Страница 117: ...116 YORK INTERNATIONAL NOTES...