YORK INTERNATIONAL
33
FORM 155.16-O3
HIGH STEAM
SUPPLY PRESS
WARNING IN
EFFECT
REMOVE HIGH STEAM
SUPPLY PRESSURE
WARNING
CLEAR HIGH STEAM
SUPPLY PRESSURE
WARNING MESSAGE
OPEN ALARM
CONTACTS TB4-89/90
CHECK PURGE PUMP
OVERLOADS INPUT
@ TB3-80
OPEN
PURGE
PUMP
OVERLOAD
WARNING IN
EFFECT
DISPLAY “WARNING-
PURGE PUMP
OVERLOADS OPEN”
CLEAR PURGE
PUMP OVERLOAD
WARNING MESSAGE
WHEN WARNING
RESET KEY
PRESSED IN
SERVICE MODE
COMPARE PURGE PUMP OPERATING
HOURS TO PURGE PUMP SERVICE
INTERVAL SETPOINT
CLOSE ALARM
CONTACTS TB4-89/90
TO SOUND AUDIBLE
ALARM UNTIL RESET
WITH WARNING
RESET KEY
> 25.5 PSIA
(175.8 kPa)
CLOSE ALARM CONTACTS
TB4-88/90 TO SOUND
AUDIBLE ALARM
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
NO
NO
YES
YES
NO
NO
YES
YES
A
A
B
C