YORK INTERNATIONAL
25
FORM 155.16-O3
BUFFALO
PUMPS
1F & 3F
OPEN
(REFRIG PUMP
SHUT-
DOWN)
DISPLAY “SYSTEM RUN-
PRIMARY LIMITED
AUTO-DECRYST”
BUFFALO
PUMPS
1F & 3F
OPEN
(REFRIG PUMP
SHUTDOWN)
CLEAR PRIMARY
LMTD AUTO
DECRYSTALLIZATION
MESSAGE
ADC
TEMP
@ RT2 >150°F
(65.6°C)
1F & 3F
CLOSED
(REFRIG PUMP
RUNNING)
ADC
TIMER
ELAPSED
LIMIT STEAM/ HOT
WATER VALVE
POSITION TO 50%
DISPLAY “SYSTEM
RUN-AUTOMATIC
DECRYSTALLIZATION”
ENERGIZE (OPEN) STABILIZER
REFRIGERANT SOLENOID
VALVE (2SOL) FOR FIRST 2
MINUTES OF NORMAL ADC
PERFORM
NORMAL ADC
PERFORM PRIMARY
LIMITED ADC
LIMIT STEAM/HOT
WATER VALVE
POSITION TO 50%
DE-ENERGIZE (CLOSE)
STABILIZER REFRIGERANT
SOLENOID VALVE (2SOL)
ADC
TIMER
ELAPSED
ADC
TEMP @
RT2 <150°F
(65.6°C)
➤
➤
➤
➤
➤
➤➤
➤
➤
➤➤
➤
➤
➤
➤
➤
➤
➤
ALLOW LOADING TO
>50% STEAM/HOT
WATER VALVE
POSITION
START 15-MINUTE
SECONDARY
LIMITED ADC TIMER
PERFORM
SECONDARY
LIMITED ADC
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
YES
YES
YES
➤
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
A
B
C
D
B
A
C
D
E
F