![York MILLENNIUM YIA-HW-14F3 Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/york/millennium-yia-hw-14f3/millennium-yia-hw-14f3_operation-manual_912660067.webp)
66
YORK INTERNATIONAL
PAGE 23
28
CLOSE SAFETY STATUS
CONTACTS TB4-42/43
DE-ENERGIZE 1R RELAY TO
CLOSE STEAM/HOT WATER
SHUTOFF VALVE
START 6 MINUTE
DILUTION CYCLE TIMER
ENTER DILUTION CYCLE
@ PAGE 35
8
EXIT DILUTION CYCLE
@ PAGE 42
*
6 MIN.
DILUTION
TIMER
ELAPSED
TERMINATE DILUTION –
SHUTDOWN ALL PUMPS
STEAM
UNIT
DE-ENERGIZE 6 SOL TO CLOSE
STEAM CONDENSATE DRAIN VALVE
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
NO
NO
YES
YES
UNIT
SW IN
STOP/
RESET
OPEN SAFETY
STATUS CONTACTS
TB4-42/43
➤
➤
➤
➤
NO
NO
YES
YES
LOCAL
OR REMOTE
START
➤
2
NO
YES
PAGE 11
HIGH
PRESSURE
SAFETY (HP1)
TRIPPED