FORM 201.10-NM1
125
YORK INTERNATIONAL
UNIT ON/OFF SWITCH, SYSTEM SWITCHES
AND OTHER CONTROLS
UNIT ON/OFF SWITCH
A master UNIT ON/OFF switch is located on the keypad.
This rocker switch allows the operator to turn the entire
chiller OFF if desired. The switch must be placed in the
ON position for the chiller to operate.
Whenever the switch is placed in the OFF position, a
STATUS display indicating the condition will be
displayed. This message is shown below:
SYSTEM SWITCHES
SYSTEM SWITCHES 1 - 4 are located on the
Microprocessor Board (See Fig. 36). These allow the
operator to selectively turn a given system on or off as
desired. On a 2-system chiller, switches 3 & 4 should be
OFF. The System Switch for a designated system must
be ON (Switch to the right) for the system to operate.
Whenever a switch is placed in the OFF position, a
STATUS message is displayed indicating that the
system does not have a Run Permissive signal. An
example of this message is shown below:
NOTE: This message will not appear if the Anti-recycle
or Anti-coincident timers are in effect and are
being displayed.
ALARM CONTACTS (ANNUNCIATION ALARM)
“Dry” contacts connected to terminals 23 and 24 of TB1
(Fig. 37) are supplied which will transition to function as
a warning whenever a fault lock-out occurs on any system
or if power is lost to the control panel. The dry contacts are
normally open (N.O.) and will close when control power is
applied to the panel, if no fault conditions are present.
When a fault occurs or power is lost, the contacts open.
A 28VDC or 120VAC external alarm circuit (supplied by
others) may be wired into the YORK supplied alarm
contacts. Any inductive load devices (relay or contactor)
supplied by the user, which are connected to the dry alarm
FIG. 35 – UNIT ON/OFF SWITCH
28164A
U N I T
S W I T C H
I S
I N
T H E
O F F
P O S I T I O N
S Y S
1
S Y S
S W I T C H
O F F
S Y S
2
S Y S
S W I T C H
O F F
UNIT
ON / OFF
SWITCH
Содержание Millennium YCAS 216X
Страница 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Страница 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Страница 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Страница 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Страница 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Страница 54: ...54 YORK INTERNATIONAL FIG 9 SYSTEM WIRING YCAS 140 246 CONNECTION DIAGRAM SYSTEM WIRING LD01466 D...
Страница 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Страница 60: ...60 YORK INTERNATIONAL FIG 12 CONNECTION DIAGRAM WYE DELTA YCAS 140 246 CONNECTION DIAGRAM WYE DELTA LD01458 D...
Страница 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Страница 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Страница 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...