<2. INSTALLATION, PIPING, AND WIRING>
2-4
IM 12B01B30-02EN 2nd Edition : June 09 , 2021-00
WARNING
● You must install external power supply switch or circuit breaker for power supply.
● The external power supply switch or a circuit breaker must comply with a current rating of
5Aor IEC60947-1 or IEC60947-3
● Yokogawa recommend installing the external power supply switch, circuit breaker and
TB820D all in the same location.
● Install the external power supply switch or circuit breaker to the place where operators
access easily. To alert users, put a label on the external power switch.
● Fix securely onto constructions or walls all power lines including wire cables of power supply
by using stanchion, cable rack, conduit or vinyl band.
Unplugged cables are dangerous and may cause an electric shock.
CAUTION
● When you open the front cover, make sure the screws are completely out of the screw
holes, and then open the front cover slowly in order not to damage the threaded parts on
the housing. If the threaded parts are damaged and the screws cannot be tightened, the
waterproof performance will deteriorate.
● Don’t lose the four screws of the front cover.
When wiring TB820D, first remove the cover of the smart unit. Provide the wiring with the cover
removed. The product is shipped with cable gland attached to the cable entry.
When protecting cables with conduits, use conduit adapters (option code: /CB3, /CD3, /CF3)
For how to provide conduit adapters, see FLXA402T Installation and Wiring
section 2.4.