<7. HART Communication>
7-46
IM 01C25W05-01EN
#
Parameter name
Factory default
value
Description
27
Ref fP2
Value of fP2 obtained under steady state operation used as a reference
for blockage detection.
28
Ref fP2 Status
Status of Ref fP2
29
Ref fP1
Value of fP1 obtained under steady state operation used as a reference
for blockage detection.
30
Ref fP1 Status
Status of Ref fP1
31
Ref BlkF
Value of BlkF obtained under steady state operation used as a reference
for blockage detection.
32
Ref BlkF Status
Status of Ref BlkF
33
Ref DPAvg
Value of DPAvg obtained under steady state operation
34
Ref DPAvg Status
Status of DP Avg
35
Lim fDPmax
See Table 7.3.2.
Upper limit of differential pressure fluctuation (Ratio fDP) used for impulse
line blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
36
Lim fDPmin
Lower limit of differential pressure fluctuation (Ratio fDP) used for impulse
line blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
37
Lim fP2max
Upper limit of module 2 side pressure fluctuation (Ratio fP2) used for
impulse line blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
38
Lim fP2min
Lower limit of module 2 side pressure fluctuation (Ratio fP2) used for
impulse line blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
39
Lim fP1max
Upper limit of module 1 side pressure fluctuation (Ratio fP1) used for
impulse line blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
40
Lim fP1min
Lower limit of module 1 side pressure fluctuation (Ratio fP1) used for
impulse line blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
41
Lim BlkFmax
Upper limit of one-side blockage level (BlkF) used for impulse line
blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
42
Lim BlkFmin
Lower limit of one-side blockage level (BlkF) used for impulse line
blockage detection.
This parameter can be entered only when Diag Mode is set to Stop.
43
Lim DPAvgmax
Upper limit of DPAvg.
This parameter can be entered only when Diag Mode is set to Stop.
44
Lim DPAvgmin
Lower limit of DPAvg.
This parameter can be entered only when Diag Mode is set to Stop.
45
Ref Lim fDPmin
7.0E-10
Lower limit of the average value of the sum of squares of differential
pressure fluctuation (Ref fDP) obtained in reference value measurement.
This is used to decide whether the reference value for impulse line
blockage detection is applicable.
This parameter can be entered only when Diag Mode is set to Stop.
46
Ref Lim fPmin
1.0E-09
Lower limit of the average value of the sum of squares of pressure
fluctuation (Ref fP2, fP1) obtained in reference value measurement.
This is used to decide whether the reference value for impulse line
blockage detection is applicable.
This parameter can be entered only when Diag Mode is set to Stop.
47
Ref Lim BlkFmax
0.5
Upper limit of the F value (Ref BlkF) obtained in reference value
measurement.
This is used to decide whether the reference value for impulse line
blockage detection is applicable.
This parameter can be entered only when Diag Mode is set to Stop.
48
Status group 15
Device status information related to the process
49
Status group 16
Device status information related to the process
50
CRatio fDP
Compensated value of fDP used to make the monitoring of Ratio fDP
easier when the flow rate change is extremely large or small.
Sqrt (fDP / Ref fDP) X │ (Ref DPAvg / DPAvg) │
Diag DP Comp Compensation must be selected.