<7. HART Communication>
7-11
IM 01C25W05-01EN
Table 7.2.2 Integral Indicator Display
Displays percentage according to the
set PV range
PV % 45.6%
The bottom area shows the
percentage and “device variable
type” assigned to PV alternately.
Displays the differential pressure in
the display range of -99999 to 99999
in the specified unit.
The bottom area shows the
differential pressure unit and DIFF.P
alternately.
Displays the module 1 side pressure
in the display range of -99999 to
99999 in the specified unit.
The bottom area shows the module 1
side pressure unit and PRESS1
alternately.
Displays the module 1 side capsule
temperature in the display range of
-99999 to 99999 in the specified unit.
The bottom area shows the
temperature unit and TEMP1
alternately.
Displays the module 2 side pressure
in the display range of -99999 to
99999 in the specified unit.
The bottom area shows the module 2
side pressure unit and PRESS2
alternately.
Displays the module 2 side capsule
temperature in the display range of
-99999 to 99999 in the specified unit.
The bottom area shows the
temperature unit and TEMP2
alternately.
Displays using the range and unit
according to the user set PV scale.
Engr LRV 0.0
Engr URV 45.0
Engr exp ×100
Engr Unit m3/min
Engr point 1
F0706.ai
Integral Indicator
Display
Description and
Related Parameters
PV percentage
(PV%)
Differential pressure
(DP)
Module 1 side pressure
(Pres 1)
Module 1 side capsule
temperature (Temp 1)
Module 2 side pressure
(Pres 2)
Module 2 side capsule
temperature (Temp 2)
User set scale PV value
(Engr Disp)
NOTE
For user set scale PV value, the process value
assigned to PV is applied to the user set scale. If
you change the PV, set the low limit (Engr LRV)
and high limit (Engr URV) of the user set scale
according to the new PV range.
To configure the integral indicator, follow steps (1) to
(4) below.
(1) Selecting the displayed content
The display content set with the Disp Out 1
parameter under Disp select is shown on the
integral indicator.
• Recalling and setting parameters
Recall
parameters
[Root menu] → Detailed setup →
Display condition → Disp select →
Disp Out 1
From the aforementioned seven types,
select the display content.
Disp Out 2 to 4 can be set in the similar manner. Set
them if necessary. In addition to the above options,
“Not used” is also available.
(2) Cyclic display
Up to four LCD screens are displayed cyclically.
The content set in each LCD screen parameter
(Disp Out 1, Disp Out 2, Disp Out 3, Disp Out 4) are
displayed in the parameter number order.
(3) Display resolution
Change the decimal place of displayed values.
• Recalling and setting the decimal place
parameter of PV%
Recall
parameters
[Root menu] → Detailed setup →
Display condition → Disp condition →
Disp PV %
reso
Set the decimal place to one of the
following two types.
Normal: Displays down to the first
decimal place
High Resolution: Displays down to the
second decimal place