<8. Maintenance>
8-14
IM 01C25W05-01EN
Indicator
NE107
(Default
Value)
Display on
Configuration
Tool
Cause
Output Operation
during Error
Countermeasure
Status
Group
Diagnostic
List
Group
AL.91
DP. SIM
C
DP Simulate Mode
(AL-91)
Under simulation mode
for differential pressure.
(AL-91)
Outputs the
Simulate-Value
value.
Check the simulation
mode.
17
Transducer Status
AL.91
P1. SIM
C
Pres 1 Simulate
Mode (AL-91)
Under simulation mode
for module 1 side
pressure. (AL-91)
AL.91
P2. SIM
C
Pres 2 Simulate
Mode (AL-91)
Under simulation mode
for module 2 side
pressure. (AL-91)
AL.91
T1. SIM
C
Temp 1 Simulate
Mode (AL-91)
Under simulation mode
for module 1 side
capsule temperature.
(AL-91)
AL.91
T2. SIM
C
Temp 2 Simulate
Mode (AL-91)
Under simulation mode
for module 2 side
capsule temperature.
(AL-91)
AL.91
PCT.SIM
C
PV % rnge Sim
Mode (AL-91)
Under simulation mode
for percent of range
output. (AL-91)
AL.91
AO. SIM
C
Loop current Sim
Mode
(AL-91)
Under simulation mode
for current output.
(AL-91)
AL.92
STS.SIM
N
Status Sim Mode
(AL-92)
Under simulation mode
for status.
(AL-92)