<Appendix 2. ILBD Check List>
A2-3
IM 01C25W05-01EN
Checklist (3/5)
Go to the following step according to the result of "Invalid Ref xx" shown in the
Diag Error
of 8th check item.
Diag Error
Check
item
Invalid Ref Pres 1
Invalid Ref Pres 2
Invalid Ref DP
→
9-a
→
9-b
: The alarm is generated.
: The alarm is not generated.
No.
Items
Parameters
Result
Example
9-a
Simulation of Blockage detection operation
• Pres 1 Side Blocking: 9-a-1
• Pres 2 Side Blocking: 9-a-2
• Both Side Blocking: 9-a-3
9-a-1
Pres 1 Side Blocking
• Close the high-pressure side valve
completely.
• Record the values of
fDP
,
fP1
,
fP2
, and
BlkF
after the certain time,
(
Diag Period X Diag Supp Count
), passed.
*: Record the value after checked that the
status is “GOOD”.
fDP*
3.74856E-08
fP2*
6.23277E-09
fP1*
1.51409E-10
BlkF
0.8658873
• Record the status of Checkbox in
Diag
Option
.
• Check that the alarms status of “A Blocking”
and “Pres 1 Side Blocking” are set.
Note: If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open
valve a little and record the updated status of the
parameters.
Diag Option
A Blocking
Large Fluct L
Large Fluct H
Pres 2 Side Blocking
Pres 1 Side Blocking
B Blocking
Invalid Ref BlkF
Invalid Ref Pres 1
Invalid Ref Pres 2
Invalid Ref DP
ILBD over range
• Check that the alarm of “Pres 1 Side
Blocking” is generated.
• Check that the alarm of “Pres 2 Side
Blocking” is not generated.
Diag Error
Pres 2 Side Blocking
Pres 1 Side Blocking