<8. Maintenance>
8-11
IM 01C25W05-01EN
Indicator
NE107
(Default
Value)
Display on
Configuration
Tool
Cause
Output Operation
during Error
Countermeasure
Status
Group
Diagnostic
List
Group
AL.30
DP.RNG
S
DP over Range.
(AL-30)
Differential pressure
exceeds specified
range. (AL-30)
Continues to output
the current value.
If the relevant signal
is assigned to PV,
the analog signal
is limited within the
variable range.
For limit values, see
subsection 3.3.1.
Check input and range
setting, and change
them as needed.
3
Transducer Status
AL.31
P1.RNG
S
Pres 1 over Range
(AL-31)
Module-1: Input
pressure exceeds
specified range. (AL-31)
AL.32
P2.RNG
S
Pres 2 over Range
(AL-32)
Module-2: Input
pressure exceeds
specified range. (AL-32)
20
AL.35
DP. HI
N
DP High Alarm
(AL-35)
Differential pressure
exceeds the specified
upper limit threshold.
(AL-35)
Continues to output
the current value.
Check the input value.
4
AL.36
DP. LO
N
DP Low Alarm
(AL-36)
Differential pressure
exceeds the specified
lower limit threshold.
(AL-36)
AL.37
P1. HI
N
Pres 1 High Alarm
(AL-37)
Module-1: Input
pressure exceeds the
specified upper limit
threshold. (AL-37)
AL.38
P1. LO
N
Pres 1 Low Alarm
(AL-38)
Module-1: Input
pressure exceeds the
specified lower limit
threshold. (AL-38)
AL.39
TMP1.HI
N
Temp 1 High Alarm
(AL-39)
Module-1: Capsule
temperature exceeds
the specified upper limit
threshold. (AL-39)
AL.40
TMP1.LO
N
Temp 1 Low Alarm
(AL-40)
Module-1: Capsule
temperature exceeds
the specified lower limit
threshold. (AL-40)
AL.41
P2. HI
N
Pres 2 High Alarm
(AL-41)
Module-2: Input
pressure exceeds the
specified upper limit
threshold. (AL-41)
21
AL.42
P2. LO
N
Pres 2 Low Alarm
(AL-42)
Module-2: Input
pressure exceeds the
specified lower limit
threshold. (AL-42)
AL.43
TMP2.HI
N
Temp 2 High Alarm
(AL-43)
Module-2: Capsule
temperature exceeds
the specified upper limit
threshold. (AL-43)
AL.44
TMP2.LO
N
Temp 2 Low Alarm
(AL-44)
Module-2: Capsule
temperature exceeds
the specified lower limit
threshold. (AL-44)
Содержание DPharp EJXC40A
Страница 1: ...User s Manual Digital Remote Sensor IM 01C25W05 01EN IM 01C25W05 01EN 4th Edition...
Страница 16: ...2 Handling Cautions 2 6 IM 01C25W05 01EN Note 6 Control Drawing...
Страница 17: ...2 Handling Cautions 2 7 IM 01C25W05 01EN...
Страница 18: ...2 Handling Cautions 2 8 IM 01C25W05 01EN...