<7. HART Communication>
7-47
IM 01C25W05-01EN
#
Parameter name
Factory default
value
Description
51
CRatio fDP Status
Status of CRatio fDP
52
NRatio fDP
When Non-compensation is selected in Diag DP Comp, NRatio fDP is
used as the monitoring value.
NRatio fDP = Sqrt (fDP / Ref fDP)
53
NRatio fDP Status
Status of NRatio fDP
54
Diag DPComp
Compensation
Flow rate compensation flag.
Sets whether Ratio fDP is monitored using CRatio fDP or NRatio fDP.
55
Diag Applicable
After the reference value is acquired, detectable blockage and fluctuation
error status is displayed.