<6. Operation>
6-11
IM 01C25W05-01EN
6.6.12 Abort Configuration
6.6.12.1 Abort Configuration (Menu)
Hold down the push button for over 2 seconds to
exit the Local Parameter Setting mode.
Hold down the button
for over 2 seconds
Proccess Value
Process Measurement Display
Process Measurement Display
1. Tag Number
2. DP Unit
3. DP LRV
4. DP URV
5. Damping Time
6. Output Mode
7. Display Out1
8. LRV-Apply Press
9. URV-Apply Press
10. Device Information
F0616.ai
Jump to the normal mode
6.6.12.2 Abort Configuration (Parameter)
To exit the configuration while editing the value,
hold down the button for over 2 seconds and select
“Save” or “Cancel”.
F0617.ai
Return to
parameter review window
Save or Cancel?
Push for
Over 2 seconds
Tag editing
(3
rd
Character)
6.6.13 Local Parameter Setting Lock
To disable parameter changes by the Local
Parameter Setting there are three different ways.
Locked features
Communication Parameter
Ext SW =disable
• External Zero
Adjustment
• Local Parameter Setting
Communication Parameter
Write Protect = On
• Local Parameter Setting
• All Communication
Parameters *
Hardware write protection
switch on CPU assembly =
D (Disable)
• Local Parameter Setting
• All Communication
Parameters *
*External Zero Adjustment is unlocked.
The above parameter setting is carried out by using
HART configuration tool. See subsection 7.2.3.11 to
13 for the setting procedure.
Reviewing local parameter setting by push button
on the integral indicator is available at any time
even when the Local Parameter Setting is locked.
6.6.14 Others
• The degree of adjustment depends on the
speed of turning the adjustment screw. Turn the
screw slowly for fine tuning and turn the screw
fast for quick tuning.
Содержание DPharp EJXC40A
Страница 1: ...User s Manual Digital Remote Sensor IM 01C25W05 01EN IM 01C25W05 01EN 4th Edition...
Страница 16: ...2 Handling Cautions 2 6 IM 01C25W05 01EN Note 6 Control Drawing...
Страница 17: ...2 Handling Cautions 2 7 IM 01C25W05 01EN...
Страница 18: ...2 Handling Cautions 2 8 IM 01C25W05 01EN...