<6. Parameter Lists>
214
IM 01E21A02-03EN
6.7 DI Function Block
Relative
Index
Index
Parameter
Name
Default Value
Write
Mode
Description
DI1 DI2 DI3
0
6000 6100 6200 Block Header
DI1:“DI1 ”
DI2:“DI2 ”
DI3:“DI3 ”
O/S
Information on this block,
such as Block Tag, DD
Revision, Execution, etc.
1
6001 6101 6201 ST_REV
0
-
Represents the revision
level of the setting
parameter of the own
block. This revision is
updated if the setpoint is
changed. Used to check
for parameter change, etc.
2
6002 6102 6202 TAG_DESC
Space (32 characters)
AUTO
Universal parameter
to store a comment
explaining tag contents.
3
6003 6103 6203 STRATEGY
1
AUTO
Universal parameter
intended to be used for
the high-level system to
separate function blocks.
4
6004 6104 6204
ALERT_KEY
1
AUTO
Key information to identify
where an alert takes place.
Generally, this parameter
is used by the high-
level system to identify
specific areas in a plant
that are under the control
of specific operators, to
separate necessary alerts
only. This is one of the
universal parameters.
5
6005 6105 6205
MODE_BLK
0x08(Auto)
0x08(Auto)
0x88(Auto, O/S)
0x08(Auto)
AUTO
-
AUTO
AUTO
Universal parameter to
show a block operation
state. Consists of Actual
mode, Target mode, Permit
mode and Normal mode.
6
6006 6106 6206
BLOCK_ERR
0x0000
-
Indicates the error statuses
related to the own block.
7
6007 6107 6207 PV_D
0x1C
0
-
-
The primary discrete value
(or process value) for
execution of the block’s
functions.
8
6008 6108 6208 OUT_D
0x1C
0
-
MAN
Indicates the value and
status of output value.
9
6009 6109 6209 SIMULATE_D
0(Bad:NonSpecific:NotLimited)
0(State 0)
0(Bad:NonSpecific:NotLimited)
0(State 0)
1(Disabled)
AUTO
AUTO
-
-
AUTO
Selects whether to use
a limit switch input which
is actually input from the
transducer block, or to use
a value specified by an
operator. If the simulation
is set to Disable, the actual
value and status will be
reflected.
10
6010 6110 6210 XD_STATE
0
AUTO
Not used for this product.
11
6011 6111 6211 OUT_STATE 0
AUTO
Not used for this product.