<Appendix 2. Integrator (It) Block>
252
IM 01E21A02-03EN
Index Parameter
Name
Default
Value
Write
Mode
View
Description
1 2 3 4
28 INTEG_TYPE UP_AUTO
(1)
1
Integration Type Setting
Value
Name
Description
1
UP_AUTO
Counts up and is
automatically reset
when TOTAL_SP is
reached.
2
UP_DEM Counts up and is reset
as demanded.
3
DN_AUTO
Counts down and is
automatically reset
when “0” is reached.
4
DN_DEM Counts down and is
reset as demanded.
5
PERIODIC
Counts up and is reset
at periods specified in
CLOCK_PER.
6
DEMAND Counts up and is reset
as demanded.
7
PER&DEM
Resets periodically or
as demanded.