![YOKOGAWA Admag TI AXG Скачать руководство пользователя страница 175](http://html.mh-extra.com/html/yokogawa/admag-ti-axg/admag-ti-axg_user-manual_911187175.webp)
<6. Parameter Lists>
174
IM 01E21A02-03EN
Relative
Index
Index
Parameter Name
Default Value
Write
Mode
Description
64
1064
FD_CHECK_PRI
0
AUTO
Shows the FD_CHECK_ALM priority
of the alarm. To activate an alarm
on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
to apply a filter to ignore values below
the specified priority on the host side.
65
1065
FD_SIMULATE
0x00000000
0x00000000
1
AUTO
-
AUTO
Parameter to simulate an alarm.
66
1066
FD_
RECOMMEN_
ACT
0
-
Indicates countermeasure for the most
important alarm.
67
1067
FD_EXTENDED_
ACTIVE_1
0x00000000
-
Parameter to initiate an alarm. For
details about bit assignment, refer to FD
and bit items in the table in Subsection
5.6.2.
68
1068
FD_EXTENDED_
ACTIVE_2
0x00000000
-
69
1069
FD_EXTENDED_
ACTIVE_3
0x00000000
-
70
1070
FD_EXTENDED_
ACTIVE_4
0x00000000
-
71
1071
FD_EXTENDED_
ACTIVE_5
0x00000000
-
72
1072
FD_EXTENDED_
ACTIVE_6
0x00000000
-
73
1073
FD_EXTENDED_
ACTIVE_7
0x00000000
-
74
1074
FD_EXTENDED_
ACTIVE_8
0x00000000
-
75
1075
FD_EXTENDED_
MAP_1
0x000010E0
AUTO
Parameter set by the user as the mask
from FD_EXTENDED_ACTIVE_1 to
DEVICE CONDITION_ACTIVE_1.
76
1076
FD_EXTENDED_
MAP_2
0x7F047F0F
AUTO
Parameter set by the user as the mask
from FD_EXTENDED_ACTIVE_2 to
DEVICE CONDITION_ACTIVE_2. For
details about bit assignment, refer to FD
and bit items in the table in Subsection
5.6.2.
77
1077
FD_EXTENDED_
MAP_3
0xE43D410B
AUTO
Parameter set by the user as the mask
from FD_EXTENDED_ACTIVE_3 to
DEVICE CONDITION_ACTIVE_3. For
details about bit assignment, refer to FD
and bit items in the table in Subsection
5.6.2.
78
1078
FD_EXTENDED_
MAP_4
0xDF3F09FF
AUTO
Parameter set by the user as the mask
from FD_EXTENDED_ACTIVE_4 to
DEVICE CONDITION_ACTIVE_4. For
details about bit assignment, refer to FD
and bit items in the table in Subsection
5.6.2.
79
1079
FD_EXTENDED_
MAP_5
0x00000400
AUTO
Parameter set by the user as the mask
from FD_EXTENDED_ACTIVE_5 to
DEVICE CONDITION_ACTIVE_5. For
details about bit assignment, refer to FD
and bit items in the table in Subsection
5.6.2.