<Appendix 4. Link Master Functions>
272
IM 01E21A02-03EN
A4.5.2 Descriptions for LM Parameters
The following describes LM parameters of this product.
Do not turn off the power to this product for 60 seconds after making a change to parameter
settings.
(1) DlmeLinkMasterCapabilitiesVariable
Bit Position
Meaning
Description
Value
B3: 0x04
LAS Schedule in
Non-volatile Memory
Indicates whether the LAS schedule can
(= 1) or cannot (= 0) be saved to the non-
volatile memory
1
B2: 0x02
Last Values Record
Supported
Indicates whether to support (= 1) or not to
support (= 0) LastValuesRecord.
0
B1: 0x01
Link Master Statistics
Record Supported
Indicates whether to support
(= 1) or not to support (= 0)
DlmeLinkMasterStatisticsRecord.
0
(2) DlmeLinkMasterInfoRecord
Sub-index
Element
Size [B]
Description
1
MaxSchedulingOverhead
1
V(MSO)
2
DefMinTokenDelegTime
2
V(DMDT)
3
DefTokenHoldTime
2
V(DTHT)
4
TargetTokenRotTime
2
V(TTRT)
5
LinkMaintTokHoldTime
2
V(LTHT)
6
TimeDistributionPeriod
4
V(TDP)
7
MaximumInactivityToClaimLasDelay
2
V(MICD)
8
LasDatabaseStatusSpduDistributionPeriod
2
V(LDDP)
(3) PrimaryLinkMasterFlagVariable
Variable which explicitly declares the LAS. Writing “TRUE” (0xFF) to this parameter in a
device causes that device to attempt to become the LAS. The request of writing “TRUE” to
this parameter in a device is rejected if the value of the same parameter in any other device
that has a smaller node address is true.
(4) LiveListStatusArrayVariable
The parameter is a variable of 32[B] and each bit represents the status of whether a device
is live (1) or not (0).
The leading bit corresponds to the device address 0x00, and the final bit to the device
address 0xFF.
For example, if there are device addresses 0x10 and 0x15 on the bus, the value is as
follows:
0x00 00 84 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00
Bit
corresponds 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 0 0 ...
0x00
0x10 0x15