<6. Parameter Lists>
173
IM 01E21A02-03EN
Relative
Index
Index
Parameter Name
Default Value
Write
Mode
Description
56
1056
FD_CHECK_
MASK
0x00000000
AUTO
Specifies a bit not to notify to the host
among 32-bit “CheckFunction” alarms
appearing on FD_CHECK_ACTIVE. For
details about bit assignment, refer to ■
Field Diagnostic.
57
1057
FD_FAIL_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when the
alarm classified into “Failed” occurs.
58
1058
FD_OFFSPEC_
ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when the
alarm classified into “Off Specification”
occurs. For details about bit assignment,
refer to FD and bit items in the table in
Subsection 5.6.2.
59
1059
FD_MAINT_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when
the alarm classified into “Maintenance”
occurs.
60
1060
FD_CHECK_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0
AUTO
-
-
-
-
Indicates contents of the alarm when the
alarm classified into “Check Function”
occurs.
61
1061
FD_FAIL_PRI
0
AUTO
Indicates the FD_FAIL_ALM priority
of the alarm. To activate an alarm
on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
to apply a filter to ignore values below
the specified priority on the host side.
62
1062
FD_OFFSPEC_
PRI
0
AUTO
Indicates the FD_OFFSPEC_ALM
priority of the alarm. To activate an
alarm on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
to apply a filter to ignore values below
the specified priority on the host side.
63
1063
FD_MAINT_PRI
0
AUTO
Indicates the FD_MAINT_ALM priority
of the alarm. To activate an alarm
on communication, it is necessary
to specify the priority for alarm
activation in advance. To activate an
alarm, set 3 or more. By sending with
priority information being added in a
communication frame when the alarm is
activated, for example, the alarm is used
to apply a filter to ignore values below
the specified priority on the host side.