5.1.9 Density Setting
The density must be set in order to measure the mass flow rate. The density can be selected
from the fixed density or density corrected with temperature.
For details about how to measure the mass flow rate or correct the density by temperature, refer
to Subsection 5.5.5.
If density is set to “0” while the mass flow rate is mapped to PV, a setting error will result.
The setting can be configured with the following parameters.
Menu path
Display
Device setup ► Detailed setup ► Pro var ► Density ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Process
Variables ► Density ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
97
Value select
Density Select
Selects one of the following
temperature-based density
corrections.
•
Fixed value
: Uses the
fixed density
•
Correction value : Uses the
corrected density
(Only available for AXG, not for
AXW).
STB
98
Unit
Density Unit
Specifies the unit of the density.
STB
99
Fixed density
Fixed Density
Specifies the value of the fixed
density.
STB
100
Std density
Standard Density
Specifies the reference
standard density value to
use the temperature-based
density correction function
(only available for AXG, not for
AXW).
STB
105
Correct density
CORRCT Density
Displays the corrected density
(only available for AXG, not for
AXW).