26
2. Main Circuits
200 V Class 3-phase Input Inverters
Note: The wire size is given for copper wire at 75
°
C.
Model
Terminal
Symbols
Screws
Tightening
Torque
N
x
m
Wires
Applicable Size
Recommended
Size
Type
mm
2
AWG
mm
2
AWG
CIMR-
J7
∗
A
20P1
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
0.8 to 1.0
0.75 to 2
18 to 14
2
14
600 V vinyl-
sheathed or
equivalent
U/T1, V/T2, W/T3
1.24
(10.97)
CIMR-
J7
∗
A
20P2
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
0.8 to 1.0
0.75 to 2
18 to 14
2
14
U/T1, V/T2, W/T3
1.24
(10.97)
CIMR-
J7
∗
A
20P4
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
0.8 to 1.0
0.75 to 2
18 to 14
2
14
U/T1, V/T2, W/T3
1.24
(10.97)
CIMR-
J7
∗
A
20P7
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
0.8 to 1.0
0.75 to 2
18 to 14
2
14
U/T1, V/T2, W/T3
1.24
(10.97)
CIMR-
J7
∗
A
21P5
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10
2
14
CIMR-
J7
∗
A
22P2
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10
3.5
12
CIMR-
J7
∗
A
23P7
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
14 to 10
5.5
10