108
O
ut
put F
un
cti
ons
Inp
ut S
ign
als
Multi-
function
Input
Four of the following input signals are selectable: Reverse run
(3-wire sequence), fault reset, external fault (NO/NC contact
input), multi-step speed operation, JOG command, accelera-
tion/deceleration time select, external baseblock (NO/NC
contact input), SPEED SEARCH command, ACCELERA-
TION/DECELERATION HOLD command, LOCAL/REMOTE
selection, communication/control circuit terminal selection,
emergency stop fault, emergency stop alarm
O
utp
ut S
ign
als
Multi-
function
Output
*3
Following output signals are selectable (1 NO/NC contact out-
put):
Fault, running, zero speed, frequency agree, frequency de-
tection (output frequency
≤
or
≥
set value), overtorque detec-
tion, minor error, baseblock, operating mode, Inverter run
ready, fault retry, UV, speed search, data output through com-
munication
Standard
Functions
Full-range automatic torque boost, slip compensation, DC in-
jection braking current/time at startup/stop, frequency refer-
ence bias/gain, frequency reference with built-in
potentiometer, [MEMOBUS communications (RS-485/422,
max. 19.2K bps) (optional)]
Ot
her
F
unc
tio
ns
Indi
cati
ons
Status
Indicators
RUN and ALARM provided as standard indicators
Digital
Operator
Provided for monitor frequency reference, output frequency,
output current
Terminals
Main circuit: screw terminals
Control circuit: plug-in screw terminal
Wiring Distance
between Inverter
and Motor
100 m or less
*5
Enclosure
Open chassis IP20
Cooling Method
Cooling fan is provided for the following models:
200 V, 0.75 kW or larger Inverters (3-phase)
200 V, 1.5 kW or larger Inverters (single-phase)
Other models are self-cooling.
En
vi
ro
nmen
ta
l Co
ndi
tion
s
Ambient
Temperature
Open chassis:
−
10 to 50
°
C (not frozen)
Humidity
95% or less (non-condensing)
Storage
Temperature
*4
−
20 to 60
°
C
Location
Indoor (free from corrosive gases or dust)
Elevation
1,000 m or less
Vibration
Up to 9.8 m/s
2
(1G) at less than 20 Hz,
up to 2 m/s
2
(0.2G) at 20 to 50 Hz
Voltage Class
200 V single-/3-phase
Model CIMR-
J7
∗
A
3-phase
20P1
20P2
20P4
20P7
21P5
22P2
23P7
Single-
phase
B0P1
B0P2
B0P4
B0P7
B1P5
-
-