9. Specifications
107
Con
tr
o
l Ch
ar
a
cte
ris
tic
s
Braking Torque
Short-term average deceleration torque
*2
0.1, 0.2 kW: 150%
0.4, 0.75 kW: 100%
1.5 kW: 50%
2.2 kW or more: 20%
Continuous regenerative torque: Approx. 20%
V/f Characteristics
Possible to program any V/f pattern
Pr
otec
tiv
e F
un
cti
ons
Motor Overload
Protection
Electronic thermal overload relay
Instantaneous
Overcurrent
Motor coasts to a stop at approx. 200% of Inverter rated cur-
rent
Overload
Motor coasts to a stop after 1 minute at 150% of Inverter rat-
ed output current
Overvoltage
Motor coasts to a stop if DC bus voltage exceed 410 V
Undervoltage
Stops when DC bus voltage is approx. 200 V or less (approx.
160 V or less for single-phase series).
Momentary Power
Loss
Following items are selectable: Not provided (stops if power
loss is 15 ms or longer), continuous operation if power loss is
approx. 0.5 s or shorter, continuous operation.
Heatsink Overheat
Protected by electronic circuit.
Stall Prevention
Level
Can be set individual level during acceleration/deceleration,
provided/not provided available during coast to a stop.
Cooling Fan Fault
Protected by electronic circuit (fan lock detection).
Ground Fault
*6
Protected by electronic circuit (rated output current level).
Power Charge Indi-
cation
RUN indicator stays ON or Digital Operator indicator stays
ON.
(Charge LED is provided for 400 V.)
ON until the DC bus voltage becomes 50 V or less.
Voltage Class
200 V single-/3-phase
Model CIMR-
J7
∗
A
3-phase
20P1
20P2
20P4
20P7
21P5
22P2
23P7
Single-
phase
B0P1
B0P2
B0P4
B0P7
B1P5
-
-