80
VS-616PS5 Programming Manual
H
Control Circuit Terminal Parameters
H5
Modbus Communication Parameters
The inverter uses communication port 6CN to communicate via MODBUS protocol
.
Setting Range: 0 to 1F
Factory Default:1F
Selects a station address for identification of the inverter during serial communica-
tion.
Selects the baud rate at which the inverter serially communicates with external
devices.
Selects the transmission parity for the 6CN MODBUS port.
H5-01 Serial Communication Station Address
A
H5-02 Serial Communication Baud Rate
A
Setting
Description
0
1200 Baud per Second
1
2400 Baud per Second
2
4800 Baud per Second
3
9600 Baud per Second
(factory default)
4
19200 Baud
<1110>
H5-03 Serial Communication Parity Selection
A
Setting
Description
0
No parity
(factory default)
1
Even parity
2
Odd parity
Section H: Control Circuit Terminal Parameters
H5 Modbus Communication Parameters