VS-616PS5 Programming Manual
77
Setting Range:
±100.0%
Factory Default:
0.0%
Sets the terminal 14 input bias level when the reference current is 4mA, (see Figure
46).
Setting Range:
0.00 to 2.00s
Factory Default:
0.00s
Sets up a filter time constant for terminals 13, 14, and 16. This filter can be used to
filter a “noisy” or fluctuating analog signal. The same filter time applies to all 3 analog
signals.
H3-11 Terminal 14 Reference ±% Bias
A
H3-12 Analog Input Filter Time Constant
A
Section H: Control Circuit Terminal Parameters
H3 Analog Inputs