66
VS-616PS5 Programming Manual
Section H: Control Circuit Terminal Parameters
H1 Digital Inputs
ing table to choose the desired response upon inputting an external fault command.
Notes:
1. N.O. = normally open contact; N.C. = normally closed contact
2. Setting “24” is the factory default.
3. Set up the external fault function according to the following tree.
External Fault Selection
Setting
Result
Input Level
Selection
Detection Method
External Fault Action
N.O.
N.C.
Always
During
Run
Ramp to
Stop
Coast to
Stop
Fast-stop
Alarm Only
÷
—
÷
—
÷
—
—
—
20
÷
—
÷
—
—
÷
—
—
24
÷
—
÷
—
—
—
÷
—
28
÷
—
÷
—
—
—
—
÷
2C
÷
—
—
÷
÷
—
—
—
22
÷
—
—
÷
—
÷
—
—
26
÷
—
—
÷
—
—
÷
—
2A
÷
—
—
÷
—
—
—
÷
2E
—
÷
÷
—
÷
—
—
—
21
—
÷
÷
—
—
÷
—
—
25
—
÷
÷
—
—
—
÷
—
29
—
÷
÷
—
—
—
—
÷
2D
—
÷
—
÷
÷
—
—
—
23
—
÷
—
÷
—
÷
—
—
27
—
÷
—
÷
—
—
÷
—
2B
—
÷
—
÷
—
—
—
÷
2F
H1 XX = “24”
Depress the Data/Enter key.
Input Level Selection
Detection Method
External Fault Action
N.O. Contact
N.C. Contact
Always
During Run
Ramp to Stop
Coast to Stop
Fast-stop
Depress
Alarm Only
the
∧
key.