VS-616PS5 Programming Manual
47
Setting Range:
0.0 to 10.0%
Factory Default:
1.0
Wiring resistance between the inverter and the motor is set by a percentage value of
the inverter’s rated voltage.
Where:
R
feed
= Percent wiring resistance between inverter and motor
R
f
= Feeder resistance (
Ω)
I
m
= Rated current (E1-04) (A)
V
b
= Inverter rated voltage (E1-03) (V)
Setting Range:
0 to 3
Factory Default:
0
Sets the winding connection configuration for the connected motor. Used only when
using the winding data look-up tables, E1-02 is not equal to 1000 (see Installation &
Quick Start Manual). Set E1-17 to the proper configuration first, then set E1-02 to the
proper winding code. This parameter is not used if E1-02=1000.
0: 1
∆
Connection:
E1-16 Motor Feeder Resistance
A
E1-17 Motor Connection Selection
A
R
feed
R
f
I
m
×
V
b
3
-------
------------------
100
×
=
T
1
T
2
T
3
·
·
·
Section E: Motor Parameters
E1 V/f Pattern