70
VS-616PS5 Programming Manual
Section H: Control Circuit Terminal Parameters
H2 Digital Outputs
Closes when run command is input from the digital operator.
• Overtorque Detection 1 - N.O. (setting: “B”)
Closes during overtorque detection 1 (L6-01, see section
L6
,
Overtorque Detec-
tion
).
• Loss of Speed Reference (setting: “C”)
Closes when the speed reference is reduced by 90% within 400ms. The inverter
will respond according to the setting of reference loss selection
(L4-05)
. After refer-
ence loss, if
L4-05
= “1,” then operation continues at 80% of the previous speed ref-
erence, and the contact closes.
•
Dynamic Braking Resistor Overheat (setting: “D”)
Closes during braking resistor overheating or a braking transistor fault.
•
Fault (setting: “E”)
Closes when a fault occurs (except CPF00 and CPF01).
•
Alarm (setting: “10”)
Closes while an alarm is displayed.
• Fault Reset (setting: “11”)
Closes while a fault is being reset.
• Timer Output (setting: “12”)
Closes when a timer contact input closes (after On-delay time elapses).
Opens when a timer contact input opens (after Off-delay time elapses).
• Speed Agree 2 (setting: “13”)
Closes whenever the output speed “agrees” with the Speed reference plus or minus
the Speed Agree Detection Width
(L4-04)
. This is used for setting up an alternate
detection width.
Fwd Run Command
Master Speed Reference
Output Speed
Reference Loss Contact
ON
OFF
80% Frequency
80%
10%
OFF
ON
OFF
ON
OFF
400ms
400ms
Figure 41 Reference Loss Timing Diagram