46
VS-616PS5 Programming Manual
Setting Range:
0 to 65.535
Ω
Factory Default:
0.000 (E1-02=1000)
Set the terminal to terminal resistance of the motor in units of 0.001
Ω.
Setting Range:
0.00 to 6
00.00
mH
Factory Default: 0.00 (E1-02=1000)
The d Axis inductance is set in units of 0.01mH.
Setting Range:
0.00 to 6
00.00
m
Η
Factory Default:
0.00 (E1-02=1000)
This parameter sets the q Axis inductance in units of 0.01mH at the time the motor-
rated load is established. Set this value equal to the setting in parameter E1-10 for
surface magnet PM motors.
Setting Range:
20.0 to 500.0 V/1000 RPM
Factory Default:
0.0 (E1-02=1000)
This parameter sets the induced voltage RMS value for the motor in units of 0.1V/
1000 RPM. Enter the induced voltage generated at 1000 RPM motor speed. Make
sure the induced voltage at the maximum speed (E1-06 does not exceed the voltage
rating of the inverter.
Do not change the value after it has been set.
Setting Range:
0.0 to 10.0%
Factory Default:
0.0
The motor’s mechanical loss is set in units of 0.1%. Used to improve torque linearity
The motor’s rated output is 100%.
E1-09 Motor Terminal to Terminal Resistance
Q
E1-10 Motor d Axis Inductance
Q
E1-11 Motor q Axis Inductance
Q
E1-13 Induced Voltage Constant
Q
E1-15 Motor Mechanical Loss
A
Section E: Motor Parameters
E1 V/f Pattern