VS-616PS5 Programming Manual
75
The following table lists the function selections for the multi-function analog inputs
(terminals 14 & 16).
H3-05 Terminal 16 Multi-function Selection
A
Setting
Function
Setting Level
0
Auxiliary Speed Reference
(factory default)
±100% / ±10V
1
Speed Gain
100% / 10V
2
Speed Bias
±100% / ±10V
7
Overtorque Level
100% / 10V
9
Reference Lower Limit
100% / 10V
A
Jump Speed
100% / 10V
B
PID Feedback
±100% / ±10V
10
Forward Torque Limit
100% / ±10V
11
Reverse Torque Limit
100% / ±10V
12
Regenerative Torque Limit
100% / ±10V
13
Torque Reference
±100% / ±10V
14
Torque Compensation
±100% / ±10V
15
Forward/Reverse Torque Limit
±100% / 10V
1F
Not Used
-
· Torque Compensation (setting: “14”)
100%
-10V
10V
-100%
0
100%
-10V
10V
0
100%
-10V
10V
0
100%
10V
-100%
0
· Auxiliary Speed Reference (setting: “0”)
· Speed Gain (setting: “1”)
· Speed Bias (setting: “2”)
· Overtorque Level (setting: “7”)
· Reference Lower Limit (setting: “9”)
· Jump Speed (setting: “A”)
· PID Feedback (setting: “B”)
· Speed Torque Limit (setting: “10”)
· Reverse Torque Limit (setting: “11”)
· Regenerative Torque Limit (setting: “12”)
· Torque Reference (setting: “13”)
· Forward/Reverse
Figure 47 Multi-function Analog Input Selection
Torque Limit
(setting: “15”)
Section H: Control Circuit Terminal Parameters
H3 Analog Inputs