With the following approach the System SLIO safety module is to be powered off and to
demounted.
1.
Switch off the DC 24V power supply of your System SLIO safety module.
2.
Demount the System SLIO safety module.
3.
Switch the F-address switch to the wished F-address.
4.
Mount the System SLIO safety module.
5.
Switch on the DC 24V power supply for the System SLIO safety module again.
6.
Start the configuration tool of the FSoE master, open the properties dialog of the
safety module and set the
reparametrization mode
. For details, refer to the manual
for your FSoE master.
7.
Wait 5s.
8.
Start the configuration tool of the FSoE master, open the properties dialog of the
safety module and reset the
reparametrization mode
again. For details, refer to the
manual for your FSoE master.
9.
Transfer the safety configuration to the FSoE master and restart the system.
3.3.1.2
Changing the F-address in the configuration
For details, refer to the manual for your FSoE master.
CAUTION!
–
Once the F-address has been changed, a complete functional test
including verification and validation of the system must be performed.
This must be documented accordingly.
–
Proceed accordingly carefully with the function test, since you must
expect faulty behaviour of the machine or system after changing the
F-address.
Online via the configura-
tion tool of the FSoE
master
VIPA System SLIO
Deployment
Setting the F-address > Changing the F-address
HB300 | SM-S | 02x-1SD10 | en | 20-02