![YASKAWA VIPA SLIO SDI Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/yaskawa/vipa-slio-sdi/vipa-slio-sdi_operating-manual_3224728050.webp)
2.9 SDO 4xDC 24V 0.5A - FSoE Parameter record set
2.9.1 FSoE application parameters
This data record set is transmitted once via the FSoE mechanism when the FSoE master
system is started.
Parameter
Sub-
index
Name
Description /
Range of values
Type
Bit
Offset
Access Default
0
Subindex 000
USINT
8
0
ro
22
1
Version identifier of the para-
metrization data structure
0x0001: first version
UINT16
16
16
rw
1
2
Module type identifier
Unique module identifier
UDINT
32
32
rw
0x0C82AE00
3
Channel 0:
Wire break detection
Condition: Channel 0, 1 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
BOOL
1
64
rw
0
4
Channel 1:
Wire break detection
Condition: Channel 0, 1 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
BOOL
1
65
rw
0
5
Channel 0, 1:
Activation mode
Condition: Channel 0, 1 acti-
vation on "activated"
0: 1-channel
1: 2-channel
BOOL
1
66
rw
1
6
Channel 0, 1:
Activation
1
0: deactivated
1: activated
BOOL
1
67
rw
1
7
Channel 2:
Wire break detection
Condition: Channel 2, 3 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
BOOL
1
68
rw
0
8
Channel 3:
Wire break detection
Condition: Channel 2, 3 acti-
vation on "activated"
0: deactivated
1: activated
Bit is not security relevant.
BOOL
1
69
rw
0
9
Channel 2, 3:
Activation mode
Condition: Channel 2, 3 acti-
vation on "activated"
0: 1-channel
1: 2-channel
BOOL
1
70
rw
1
10
Channel 2, 3:
Activation
1
0: deactivated
1: activated
BOOL
1
71
rw
1
Record set 0x8000
VIPA System SLIO
Product description
SDO 4xDC 24V 0.5A - FSoE Parameter record set > FSoE application parameters
HB300 | SM-S | 02x-1SD10 | en | 20-02
50