Order no.
022-1SD10
Lamp load
5 W
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
not possible
Actuation of digital input
ü
Switching frequency with resistive load
max. 50 Hz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 10 Hz
Internal limitation of inductive shut-off voltage
L+ (-45 V)
Short-circuit protection of output
yes, electronic
Trigger level
1.7 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
Output data size
4 Bit
Status information, alarms, diagnostics
Status display
green LED per channel
Interrupts
yes, parameterizable
Process alarm
no
Diagnostic interrupt
yes, parameterizable
Diagnostic functions
yes, parameterizable
Diagnostics information read-out
possible
Supply voltage display
green LED
Group error display
red SF LED
Channel error display
red ERR-LED and yellow ER2-LED
Isolation
Between channels
-
Between channels of groups to
-
Between channels and backplane bus
ü
Insulation tested with
DC 500 V
PWM data
PWM channels
-
PWM time basis
-
Period length
-
Minimum pulse width
-
Type of output
-
Safety
Safety protocol
-
VIPA System SLIO
Product description
SDO 4xDC 24V 0.5A - Technical data
HB300 | SM-S | 02x-1SD10 | en | 20-02